Input Calibration 
Calibration Steps 
Use the following steps when calibrating an input. 
Step  Action 
1 
Find the minimum and maximum range values for your PV input range from Table 5-1. 
2 
Disconnect the field wiring and find out what equipment you will need to calibrate. 
3 
Wire the calibrating device to your controller according to the set up wiring instructions 
for your particular input (Subsection 5.4). 
4 
Follow the calibration procedure given for Input #1 or Input #2 (Subsection 5.5). 
5.2  Minimum and Maximum Range Values 
Select the Range Values 
Calibrate the controller for the minimum (0 %) and maximum (100 %) range values of 
your particular input type. Two input controllers will need to have each input calibrated 
separately. 
Select the Voltage, Current or Resistance equivalents for 0 % and 100 % range values 
from Table 5-1. Use these values when calibrating your controller. 
Table 5-1  Voltage, Milliamp and Resistance Equivalents for Input  Range Values 
PV Input Range  Range Values Sensor Type 
°F  °C  0 %  100 % 
Thermocouples 
(per ITS-90) 
   
B 
    0  to  3300    –18  to  1816  –0.100 mV  13.769 mV 
E TC H 
  –454  to  1832    –270  to  1000  –9.835 mV  76.373 mV 
E TC L 
  –200  to  1100    –129  to  593  –6.472 mV  44.455 mV 
J TC H  
  0  to  1600    –18  to  871  –0.886 mV  50.060 mV 
J TC M 
20 to 900  –7  to 482 
–0.334 mV 
26.400 mV 
J TC L 
20 to 550  –7 to 288  –0.334 mV  15.650 mV 
K TC H  
0 to  2400  –18 to 1816  –0.692 mV  52.952 mV 
K TC M 
–20 to 1200  –29 to 649  –1.114 mV  26.978 mV 
K TC L 
–20 to 750  –29 to 399  –1.114 mV  16.350 mV 
NNM H 
32 to 2500    0  to 1371  0.000 mV  71.773 mV 
NNM L  
32 to 1260    0  to  682  0.000 mV  31.825 mV 
NIC H  
  0  to  2372    –18  to 1300  –0.461 mV  47.513 mV 
NIC L 
  0  to  1472    –18  to  800  -0.461 mV  28.455 mV 
R TC 
  0  to  3100    –18  to 1704  –0.090 mV  20.281 mV 
12/04  UDC3200 Universal Digital Controller Product Manual  133