Modbus Read, Write and Override Parameters plus Exception Codes 
10.4  Miscellaneous Read Onlys 
10.4.1  Register Addresses for Read Onlys 
The identifying register addresses listed in Table 10-3 represent some information that is 
Read only. No Writes allowed. 
Table 10-3  Miscellaneous Read Onlys  
Parameter 
Description 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
  Hex  Decimal       
Software Type  009D   157  INT  RD  READ only (UDC3200) 
50 = UDC3200  
Software Version  00A7  167  INT  RD  READ only 
Value less than 255 
 
10.4.2  SetPoint Program Read Only Information 
The identifying register addresses listed in Table 10-4 represent some information for 
SetPoint Programming that is Read only. No Writes allowed. 
Table 10-4  SetPoint Program Read Only Information 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
  Hex  Decimal       
Present SPP 
Segment Number 
00FB   251  INT  RD  1 – 12  
Segment Time 
Remaining in 
Minutes 
00FC  252  INT  RD  0 – 59 Minutes 
Segment Time 
Remaining in 
Hours 
00FD  253  INT  RD  0 – 99 Hours 
Cycles Remaining  00FE  254  INT  RD  0 – 100 
Current Cycle 
Number 
00FF  255  INT  RD  0 – 100 
 
 
188  UDC3200 Universal Digital Controller Product Manual  12/04