Configuration 
3.14   Alarms Set Up Group 
Introduction 
An alarm is an indication that an event that you have configured (for example—Process 
Variable) has exceeded one or more alarm limits. There are two alarms available. Each 
alarm has two setpoints. You can configure each of these two setpoints to alarm on 
various controller parameters. 
There are two alarm output selections, High and Low. You can configure each setpoint to 
alarm either High or Low. These are called single alarms. 
You can also configure the two setpoints to alarm on the same event and to alarm both 
high and low. A single adjustable Hysteresis of 0 % to 100 % is configurable for the 
alarm setpoint. 
See Table 2-3 in the Installation section for Alarm relay contact information. 
The prompts for the Alarm Outputs appear whether or not the alarm relays are physically 
present. This allows the Alarm status to be shown on the display and/or sent via 
communications to a host computer. 
Function Prompts 
Table 3-14 ALARMS Group Function Prompts 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
A1S1 VAL 
Value in engineering units 
ALARM 1 SETPOINT 1 VALUE—This is the value 
at which you want the alarm type chosen in prompt 
A1S1TYPE to actuate. The value depends on what 
the setpoint has been configured to represent. No 
setpoint is required for alarms configured for 
Communications SHED. For SP Programming the 
value is the segment number for which the event 
applies. 
This prompt does not appear for “Alarm on Manual” 
type alarm. For example: A1S1TYPE = MANUAL. 
A1S2 VAL 
Value in engineering units 
ALARM 1 SETPOINT 2 VALUE—This is the value 
at which you want the alarm type chosen in prompt 
A1S2TYPE to actuate. 
The details are the same as A1S1 VAL. 
A2S1 VAL 
Value in engineering units 
ALARM 2 SETPOINT 1 VALUE—This is the value 
at which you want the alarm type chosen in prompt 
A2S1TYPE to actuate. 
The details are the same as A1S1 VAL. 
A2S2 VAL 
Value in engineering units 
ALARM 2 SETPOINT 2 VALUE—This is the value 
at which you want the alarm type chosen in prompt 
A2S2TYPE to actuate.  
The details are the same as A1S1 VAL. 
12/04  UDC3200 Universal Digital Controller Product Manual  87