Monitoring and Operating the Controller 
Table 4-24  Program Contents 
Associated 
Prompts 
Contents  Definition 
STRT SEG  Start segment 
number 
The start segment number designates the number of the first 
segment. 
Range = 1 to 11 
END SEG  End segment 
number 
The end segment number designates the number of the last 
segment, it must be a soak segment (even number).  Range = 
2 to 12 
RECYCLES Recycle number 
The recycle number allows the program to recycle a specified 
number of times from beginning to end.  Range = 0 to 99 
STATE Program state 
The program state selection determines the program state 
after completion. 
The selections are: 
•  DISABLE = program is disabled (so program value 
changed to DISABLE) 
•  HOLD = program on hold 
PROG END  Program 
termination state 
The program termination state function determines the status 
of the controller upon completion of the program. 
The selections are: 
•  LAST = controls to last setpoint 
•  FAILSAFE = manual mode and failsafe output. 
KEYRESET 
(ToBEGIN) 
Reset Program 
to Beginning 
When enabled, this selection allows you to reset the program 
via the keyboard to the beginning of the program. 
KEYRESET 
(RERUN) 
Rerun current 
segment 
When enabled, this selection allows you to reset the program 
via the keyboard to the beginning of the current segment. 
HOTSTART Hot Start 
This function determines whether LSP1 or PV is used as the 
setpoint when the program is initially changed from HOLD to 
RUN. 
The selections are: 
DISABLE =  When the program is initially changed from HOLD 
to RUN the present LSP1 value is captured as 
the default setpoint. If the program is terminated 
or the power cycled before the program has 
completed, the LSP1 is used as the control 
setpoint.  The beginning segment uses this value 
as the initial ramp setpoint. 
ENABLE =   When the program is initially changed from HOLD 
to RUN the present PV value is captured and 
used as the beginning setpoint value for the ramp 
segment.  If the program is terminated before 
completion, the setpoint value will revert back to 
the PV value captured at the initial HOLD to RUN 
transition.  If the power is cycled before program 
completion, upon power-up the setpoint is set to 
126  UDC3200 Universal Digital Controller Product Manual  12/04