Configuration
3.3 Configuration Procedure
Introduction
Each of the Set Up groups and their functions are pre-configured at the factory.
The factory settings are shown in Table 3-4 through Table 3-14 that follow this
procedure.
If you want to change any of these selections or values, follow the procedure in Table
3-3. This procedure tells you the keys to press to get to any Set Up group and any
associated Function parameter prompt.
Procedure
ATTENTION
The prompting scrolls at a rate of 2/3 seconds when the SET UP or FUNCTION key is held in.
Also,
or keys will move group prompts forward or backward at a rate twice as fast.
Table 3-3 Configuration Procedure
Step Operation Press Result
1
Enter Set Up
Mode
SetupSetup
Upper Display = SETUP
Lower Display = TUNING (This is the first Set Up Group title)
2
Select any Set
Up Group
SetupSetup
Sequentially displays the other Set Up group titles shown in the
prompt hierarchy in Table 3-2 Configuration Prompt Hierarchy.
You can also use the or keys to scan the Set Up groups
in both directions. Stop at the Set Up group title that describes the
group of parameters you want to configure. Then proceed to the
next step.
3
Select a Function
Parameter
Function
FunctionFunction
Upper Display = the current value or selection for the first function
prompt of the selected Set Up group.
Lower Display = the first Function prompt within that Set Up group.
Sequentially displays the other function prompts of the Set Up
group you have selected. Stop at the function prompt that you want
to change, then proceed to the next step.
4
Change the
Value or
Selection
or
Increments or decrements the value or selection that appears for
the selected function prompt. If you change the value or selection
of a parameter while in Set Up mode but then decide not to enter it,
press the
MAN/AUTO key once. This will recall the original
configuration. This “recall” procedure does not work for a Field
Calibration process. Field Calibration is a one-way operation.
5
Enter the Value
or Selection
Function
FunctionFunction
Enters value or selection made into memory after another key is
pressed.
6
Exit Configuration
Lower
Display
Lower
Display
Lower
Display
Exits configuration mode and returns controller to the same state it
was in immediately preceding entry into the Set Up mode. It stores
any changes you have made.
If you do not press any keys for 30 seconds, the controller times out
and reverts to the mode and associated display used prior to entry
into Set Up mode.
12/04 UDC3200 Universal Digital Controller Product Manual 39