Monitoring and Operating the Controller 
4.15 Setting a Failsafe Output Value for Restart After a Power Loss 
Introduction 
If the power to the controller fails and power is reapplied, the controller goes through the 
power up tests, then goes to a user configured FAILSAFE OUTPUT VALUE. 
Set a Failsafe Value 
Table 4-21  Procedure for Setting a Failsafe Value  
Step  Operation  Press  Result 
1 
Select Control  
Set-up Group 
SetupSetup
 
Until you see: 
Upper Display = SET  
Lower Display = CONTROL 
2 
Select Failsafe 
Function Prompt 
Function
FunctionFunction
 
You will see: 
Upper Display = (range) 
within the range of the Output 0 to 100 for all output types 
except Three Position Step 
Three Position Step 
  0 = motor goes to closed position 
  100 = motor goes to open position 
Lower Display = F’SAFE 
3 
Select a value 
or  
To select a failsafe output value in the upper display 
4 
Return to Normal 
Display 
Lower
Display
Lower
Display
Lower
Display
 
At power up, the output will go to the value set. 
 
12/04  UDC3200 Universal Digital Controller Product Manual  121