Configuration 
3.10   Input 2 Set Up Group 
Introduction 
This data deals with various parameters required to configure Input 2. 
Function Prompts 
Table 3-10 INPUT 2 Group Function Prompts 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
IN2 TYPE 
 ATTENTION  
Changing the input 
type will result in the 
loss of Field 
Calibration values and 
will restore Factory 
Calibration values. 
Selecting Position 
Proportional Control in 
the Output Setup 
Group forces Input 2 
to the Slidewire 
Selection. 
 
 
DISABLE 
B TC 
E TC H 
E TC L 
J TC H  
J TC M 
J TC L 
K TC H  
K TC M 
K TC L 
NNM H 
NNM L  
NIC H  
NIC L 
R TC 
S TC 
T TC H 
T TC L 
W TC H 
W TC L 
100 PT 
100 LO 
200 PT 
500 PT 
RAD RH 
RAD RI 
0-20mA 
4-20mA 
0-10mV 
0-50mV 
0-100mV 
0-5 V 
1-5 V 
0-10 V 
TC DIFF 
SLIDEW 
INPUT 2 ACTUATION TYPE – This selection 
determines what actuation you are going to use for 
Input 2. 
DISABLE—Disables Input. 
B TC—B Thermocouple 
E TC H—E Thermocouple High 
E TC L—E Thermocouple Low 
J TC H—J Thermocouple High  
J TC M—J Thermocouple Med 
J TC L—J Thermocouple Low 
K TC H—K Thermocouple High  
K TC M—K Thermocouple Med 
K TC L—K Thermocouple Low 
NNM H—Ni-Ni-Moly Thermocouple High 
NNM L—Ni-Ni-Moly Thermocouple Low  
NIC H—Nicrosil-Nisil Thermocouple High  
NIC L—Nicrosil-Nisil Thermocouple Low 
R TC—R Thermocouple 
S TC—S Thermocouple 
T TC H—T Thermocouple High 
T TC L—T Thermocouple Low 
W TC H—W5W26 Thermocouple High 
W TC L—W5W26 Thermocouple Low 
100 PT—100 Ohm RTD High 
100 LO—100 Ohm RTD Low 
200 PT—200 Ohm RTD 
500 PT—500 Ohm RTD 
RAD RH—Radiamatic RH 
RAD RI—Radiamatic RI 
0-20mA—0 to 20 Milliamperes 
4-20mA—4 to 20 Milliamperes 
0-10mV—0 to 10 Millivolts 
0-50mV—0 to 50 Millivolts 
0-100mV—0 to 100 Millivolts 
0-5 V—0 to 5 Volts 
1-5 V—1 to 5 Volts 
0-10 V—0 to 10 Volts 
TC DIFF—Thermocouple Differential 
SLIDEW—Slidewire (For Position Proportional 
Applications) 
68  UDC3200 Universal Digital Controller Product Manual  12/04