Input Calibration 
Step  Operation  Press  Result 
3 
Calibrate 100 % 
Function
FunctionFunction
 
You will see: 
Check the Cold 
Junction 
Temperature 
 
Function
FunctionFunction
 
The calculations for zero and span are now stored and you 
will see: 
Upper Display = The cold junction temperature at the rear 
terminals 
Lower Display = CJTEMP  
The value in the upper display is in tenths of a degree. It is 
the current reading of the temperature as measured at the 
thermocouple terminals and recognized by the controller. 
You can change this value, if it is in error, using the 
or keys. 
WARNING: The accuracy of the controller is directly 
affected by the accuracy of this value.  It is recommended 
that this value not be changed under normal circumstances. 
5 
Exit the 
Calibration Mode 
Function
FunctionFunction
then 
The controller stores the calibration constants and exits the 
calibration mode. 
 
 
Lower
Display
Lower
Display
Lower
Display
 
 
 
4 
5.6  Restore Input Factory Calibration 
Introduction 
The factory calibration constants for all the input actuation types that can be used with 
the controller are stored in its non-volatile memory. Thus, you can quickly restore the 
“Factory Calibration” for a given input actuation type by simply changing the actuation 
type to another type and then changing it back to the original type.  
Refer to Table 5-10  Restore Factory Calibration for procedure 
12/04  UDC3200 Universal Digital Controller Product Manual  141