Monitoring and Operating the Controller 
•  A Ramp Time (TIMIN) in minutes has been configured 
•  A final setpoint value (FINLSP) has been configured.  See Subsection 3.5 – 
Configuration group “SPRAMP” for details. 
Operation 
Running a Setpoint Ramp includes starting, holding, viewing the ramp, ending the ramp 
and disabling it.  See Table 4-23. 
Table 4-23  Running A Setpoint Ramp 
Step  Operation  Press  Result 
Select Automatic 
Mode 
1 
Man
Auto
Man
Auto
Man
Auto
2 
Set Start Setpoint 
Lower
Display
Lower
Display
Lower
Display
 
Until start SP value is in lower display 
Upper Display = “H” and PV value 
Lower Display = SP and start SP value 
3 
Start the Ramp 
Run
Hold
Run
Hold
Run
Hold
 
You will see 
Upper Display = “R” and a changing PV value 
Lower Display = SP and a changing SP value increasing 
or decreasing toward the final SP value 
4 
Hold/Run the 
Ramp 
Run
Hold
Run
Hold
Run
Hold
 
This holds the ramp at the current setpoint value.  Press 
again to continue. 
5 
View the 
remaining ramp 
time 
Until you see 
Upper Display = PV value 
Lower Display = RAMPXXXM (time remaining in 
minutes) 
6 
End the Ramp 
Lower
Display
Lower
Display
Lower
Display
 
When the final setpoint is reached, “R” changes to “H” in 
the upper display and the controller operates at the new 
final setpoint. 
7 
Disable SPRAMP 
  See Section 3 – Configuration group “SPRAMP” for 
details. 
“A” indicator is on. 
Upper Display = “H” and PV value 
Lower Display = SP and Present value 
 
 
Power Outage 
If power is lost during a ramp, upon power-up the controller will be in HOLD and the 
setpoint value will be the setpoint value prior to the beginning of the setpoint ramp. 
The ramp is placed in hold at the beginning. 
Configure the mode at Set Up Group “CONTROL”, function prompt “PWR MODE”.  
See Subsection 3.11 – CONTROL SETUP GROUP Prompts. 
 
124  UDC3200 Universal Digital Controller Product Manual  12/04