Honeywell UDC3200 - Control; Table 10-16 Set-Up Group - Control

Honeywell UDC3200
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Read, Write and Override Parameters plus Exception Codes
10.7.8 Control
Table 10-16 lists all the register addresses and ranges or selections for the function
prompts in Set-up Group Control.
Table 10-16 Set-up Group – Control
Parameter
Description
Register
Address
Data
Type
Data Range or
Enumerated Selection
Hex Decimal
PV Source 0085 133 INT R/W 0 = Input 1
1 = Input 2
2 = Input Algorithm 1
Tuning
Parameter
Selection
00AC 172 INT R/W 0 = One set only
1 = 2 sets keyboard selected
2 = 2 sets with PV automatic
switchover
3 = 2 sets with setpoint (SP)
automatic switchover
Automatic
Switchover
Value (used with
172 selection 2
or 3)
0038 056 FP R/W Within the PV Range in
engineering units
Local Setpoint
Source (Number
of LSPs)
00AD 173 INT R/W 0 = One Local Setpoint
1 = Two Local Setpoints
2 = Three Local Setpoints
Power Up Mode
Recall
0082 130 INT R/W
Control Setpoint
Mode Mode
0 = MAN LSP
1 = AUTO LSP
2 = AUTO Last RSP
3 = LAST Last SP
4 = LAST Last Local SP
RSP Source 0083 131 INT R/W 0 = None
1 = Input 2
Setpoint
Tracking
008A 138 INT R/W 0 = None
1 = LSP = PV (when in
Manual)
2 = LSP = RSP (when
switched)
Auto Bias 0089 137 INT R/W 0 = Disable
1 = Enable
Access
12/04 UDC3200 Universal Digital Controller Product Manual 209