Input Calibration 
PV Input Range  Range Values Sensor Type 
°F  °C  0 %  100 % 
S TC 
  0  to  3100    –18  to 1704  –0.092 mV  17.998 mV 
T TC H 
  -300  to  700    –184  to  371  –5.341 mV  19.097 mV 
T TC L 
  -200  to  500    –129  to  260  –4.149 mV  12.574 mV 
W TC H 
  0  to  4200    –18  to  2315  –0.234 mV  37.075 mV 
W TC L 
  0  to  2240    –18  to  1227  –0.234 mV  22.283 mV 
Thermocouple 
Differential * 
–50 to 150  –46 to  66  –1.54 mV  4.62 mV 
Honeywell 
Radiamatic 
 
 
Type RH 
Type RI ** 
 0 to  3400 
 0 to  3400 
–18 to 1871 
–18 to 1871 
0.00 mV 
0.00 mV 
57.12 mV 
60.08 mV 
RTD 
Alpha = 0.00385 per 
IEC-60751 (1995) 
   
100 ohms  
100 ohms (low)  
200 ohms 
500 ohms 
 –300 to 1200 
  –300  to    300 
 –300 to 1200 
 –300 to 1200 
 –184 to 649 
 –184 to 149 
 –184 to 649 
 –184 to 649 
25.202 ohms 
25.202 ohms 
50.404 ohms 
126.012 ohms 
329.289 ohms 
156.910 ohms 
658.578 ohms 
1646.445 ohms 
Linear 
Milliamps 
 
4 to 20 mA 
0 to 20 mA 
 
4.00 mA 
0.00 mA 
 
20.00 mA 
20.00 mA 
Millivolts 
0 to   10 mV 
0 to   50 mV 
0 to 100 mV 
0.00 mV 
0.00 mV 
0.00 mV 
10.00 mV 
50.00 mV 
100.00 mV 
Volts 
1 to   5 Volts  
0 to   5 Volts 
0 to 10 Volts 
1.00 Volts  
0.00 Volts 
0.00 Volts 
5.00 Volts  
5.00 Volts 
10.00 Volts 
Carbon 
Oxygen 
    0 to 1250 mV  
–30 to  510 mV 
0.00 mV  
–30.00 mV 
1250.00 mV  
510.00 mV 
 
*  The Factory Calibrated millivolt values for the Thermocouple Differential Input are for a pair 
of J thermocouples at an ambient temperature mean of 450°F / 232°C.  Other thermocouple 
types and ambient temperature means may be accomplished via Field Calibration of the input, 
with the range value limits being –4 mV to +16 mV for the zero and span values. 
** The range values for Radiamatic Type RI are customer configurable within the limits shown. 
 
134  UDC3200 Universal Digital Controller Product Manual  12/04