Loading...
Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Input 2
Transmitter
Characterization
00AB 171 INT R/W 0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = R TC
14 = S TC
15 = T TC H
16 = T TC L
17 = W TC H
18 = W TC L
19 = 100 PT RTD
20 = 100 PT LO RTD
21 = 200 PT RTD
22 = 500 PT RTD
23 = Radiamatic RH
24 = Radiamatic RI
25 = Linear
26 = Square Root
Input 2 High
Range Value
0023 035 FP R/W –999. to 9999. Engineering
Units
Input 2 Low
Range Value
0024 036 FP R/W –999 to 9999. Engineering
Units
Input 2 Ratio 0025 037 FP R/W –20.00 to 20.00
Input 2 Bias 0026 038 FP R/W –999 to 9999. Engineering
Units
Input 2 Filter 002B 043 FP R/W 0 to 120 seconds
Input 2
Emmissivity
002C 044 FP R/W 0.01 to 1.00
12/04 UDC3200 Universal Digital Controller Product Manual 207