Modbus Read, Write and Override Parameters plus Exception Codes
Parameter Register Data Access Data Range or
Description Address Type Enumerated Selection
Hex Decimal
TPSC Failsafe
Output
00B8 184 INT R/W 0 = Motor goes to closed
position (0%)
1 = Motor goes to open
position (100%)
Manual Output 0071 113 FP R/W 0 to 100%
Automatic
Output
0072 114 FP R/W 0 to 100%
Proportional
Band Units
0094 148 INT R/W 0 = Gain
1 = Proportional band
0095 149 INT R/W 0 = Minutes
1 = RPM
Reset Units
12/04 UDC3200 Universal Digital Controller Product Manual 211