Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Digital Input
#1
00BA 186 INT R/W
0 = None
1 = To Manual
2 = To Local Setpoint #1
3 = To Local Setpoint #2
4 = To Local Setpoint #3
5 = To Direct Action
6 = To Hold Ramp
7 = To PID Set #2
8 = PV = Input 2
9 = Unused
10 = Rerun SPP Cycle
11 = To Run Ramp
12 = Reset SP Program
13 = Inhibit Reset
14 = To Manual/Failsafe
Output
15 = Disable Keyboard
16 = To Automatic Output
17 = To Timer
18 = To Auto/Man Station
19 = Initiate Limit Cycle
Tuning
20 = Setpoint Initialization
(SP=PV)
21 = Output Tracks Input 2
22 = Unused
23 = Unused
24 = To RSP
25 = Unused
26 = External Reset Feedback
27 = To Purge
28 = To Low Fire
29 = Manual Latching
30 = Unused
31 = Unused
32 = PV Hold