Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
ACCUTUNE 
 
DISABLE 
TUNE 
ACCUTUNE III 
DISABLE —Disables the Accutune function. 
DEMAND TUNING—If TUNE is selected, and tuning 
is initiated through the operator interface or digital 
input (if configured), the algorithm calculates new 
tuning parameters and enters them into the tuning 
group. This tuning requires no process knowledge 
and does not require line out for initialization. 
DUPLEX 
 
 
DUPLEX ACCUTUNING III – These prompts only 
appear when a duplex output type has been 
configured. 
This prompt only 
appears when a 
Duplex Control 
Algorithm has been 
configured 
MANUAL 
MANUAL – Tune manually using LSP 1 and LSP 2 
values.  LSP 1 is used to derive tuning parameters 
associated with HEAT (output > 50 %).  LSP 2 is 
used to derive tuning parameters associated with 
COOL (output < 50 %). 
 
AUTO 
AUTOMATIC – Tuning is performed automatically 
on both HEAT and COOL sequentially.  LSP 1 is 
used for HEAT tuning and LSP 2 is used for COOL 
tuning.  To initiate tuning, either LSP 1 or LSP 2 
must be in use. 
 
DISABLE 
DISABLE – The current SetPoint is used to derive a 
single set of blended tuning parameters.  This tuning 
is performed over the range of the output limits 
similar to Simplex Tuning.  The Tuning Parameters 
derived are placed into both the HEAT and COOL 
tune sets (PID 1 and PID 2). 
AT ERROR 
(Read Only) 
 
 
ACCUTUNE ERROR STATUS—When an error is 
detected in the Accutune process, an error prompt 
will appear. 
 
NONE 
NONE—No errors occurred during last Accutune 
procedure. 
 
RUNNING 
RUNNING—An Accutune process is still active 
checking process gain, even though “T” is not lit. It 
does not affect keyboard operation. 
 
ABORT 
CURRENT ACCUTUNE PROCESS ABORTED—
Caused by one of the following conditions: 
  •  changing to manual mode 
  •  digital input detected  
  •  in heat region of output but a cool output was 
calculated, or vice versa. 
 
SP2 
SP2—LSP2 not configured or a Setpoint other than 
LSP1 or LSP2 is in use. 
12/04  UDC3200 Universal Digital Controller Product Manual  49