Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
PCT CO 
0.020 to 0.350 (fractional 
percent of CO) 
PERCENT CARBON is only applicable when 
Carbon Potential is selected. Enter the value in 
percent carbon monoxide that is applicable for the 
enriching gas used in fractional form. 
FOR EXAMPLE: 
Natural Gas = 20.0 % CO, then setting is 0.200 
Propane Gas = 23.0 % CO, setting is 0.230 
ALG1 BIAS 
-999 to 9999 floating (in 
engineering units) 
INPUT ALGORITHM 1 BIAS—Does not apply to 
selections: FFWRD, FFWDMU, HISEL or LOSEL. 
PCT H2 
1.0 to 99.0 (% H
2
) 
HYDROGEN CONTENT FOR DEWPOINT is only 
applicable when Dewpoint is selected. Enter a value 
for the percentage of Hydrogen content that is 
applicable. 
Math Algorithm Notes: 
1.  Calculation ranges for the Math Algorithms are set via CALC HI and CALC LO parameters and 
are between –999. and 9999.  The SP High and Low values (SP Range) are independent of 
these settings and can be any value between –999. and 9999. 
2.  The CALC HI and CALC LO values determine the range limits for the SP High and Low values 
for the Weighted Average, Summer, Hi Select and Low Select algorithms.  
3.  If the Ratio for Input 2 is set to 0.0, then a constant value may be used for the Input 2 value via 
the Input 2 Bias setting.  For this configuration, the Input 2 low range and the Sooting diagnostic 
messages are disabled.  
 
 
12/04  UDC3200 Universal Digital Controller Product Manual  57