Configuration
Function Prompt Selections or
Parameter
Lower Display
Range of Setting
Upper Display
Definition
CUR OUT
DISABLE
INPUT 1
INPUT 2
PV
DEV
OUTPUT
SP
LSP
RSP
IN ALG 1
CURRENT OUTPUT – If Current Output #1 is not
used to perform one of the above output algorithms,
it may be used to perform an Auxiliary Output
function.
DISABLE
INPUT 1
INPUT 2
PV (Process Variable)
DEVIATION
OUTPUT
SETPOINT
LOCAL SETPOINT
REMOTE
INPUT ALGORITHM 1
LOW VAL
Low Scale Value within
the range of the selected
variable to represent the
minimun output (0 or 4
mA)
CURRENT OUTPUT LOW SCALING FACTOR
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
HIGH VAL
High Scale Value within
the range of the selected
variable to represent the
maximum output (20 mA)
CURRENT OUTPUT HIGH SCALING FACTOR
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
CO RANGE
4-20mA
0-20mA
CURRENT OUTPUT RANGE allows the user to
easily select 4-20 mA output or 0-20 mA output
operation without the need for recalibration of the
instrument.
ATTENTION Changing the Current Output Range
will result in the loss of Field Calibration values and
will restore Factory Calibration values.
12/04 UDC3200 Universal Digital Controller Product Manual 63