Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
CUR OUT 
 
 
 
DISABLE 
INPUT 1 
INPUT 2 
PV 
DEV 
OUTPUT 
SP 
LSP 
RSP 
IN ALG 1 
CURRENT OUTPUT – If Current Output #1 is not 
used to perform one of the above output algorithms, 
it may be used to perform an Auxiliary Output 
function. 
DISABLE 
INPUT 1 
INPUT 2 
PV (Process Variable) 
DEVIATION 
OUTPUT 
SETPOINT 
LOCAL SETPOINT 
REMOTE 
INPUT ALGORITHM 1 
LOW VAL 
Low Scale Value within 
the range of the selected 
variable to represent the 
minimun output (0 or 4 
mA) 
CURRENT OUTPUT LOW SCALING FACTOR—
Used only when CUR OUT is any selection other 
than DISABLE.  This is a value in engineering units 
used to represent all CUR OUT parameters except 
Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %.  However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
HIGH VAL 
High Scale Value within 
the range of the selected 
variable to represent the 
maximum output (20 mA) 
CURRENT OUTPUT HIGH SCALING FACTOR—
Used only when CUR OUT is any selection other 
than DISABLE.  This is a value in engineering units 
used to represent all CUR OUT parameters except 
Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %.  However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
CO RANGE 
4-20mA  
0-20mA 
CURRENT OUTPUT RANGE allows the user to 
easily select 4-20 mA output or 0-20 mA output 
operation without the need for recalibration of the 
instrument. 
 ATTENTION   Changing the Current Output Range 
will result in the loss of Field Calibration values and 
will restore Factory Calibration values. 
 
12/04  UDC3200 Universal Digital Controller Product Manual  63