Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
RSP SRC 
 
 
 
REMOTE SETPOINT SOURCE—This selection 
determines what your remote setpoint source will be 
when toggled by the SP Select key or Digital Input. 
 
NONE 
INPUT 2 
IN ALG1 
NONE—No remote setpoint. 
INPUT 2—Remote Setpoint is Input 2. 
IN AL1—Remote Setpoint using Input 1 algorithm. 
 ATTENTION   To cycle through the available local 
setpoints and remote setpoint, press and hold in the 
SP 
Select
SP 
Select
SP 
Select
key. When the key is released, the setpoint 
selection currently displayed will be the new setpoint 
selection. 
AUTOBIAS 
 
 
 
 
 
DISABLE 
ENABLE 
AUTOBIAS is used for bumpless transfer when 
transferring from local setpoint to remote setpoint. 
Auto Bias calculates and adds a bias to remote 
setpoint input each time a transfer is made. 
Only available if no tracking is selected. 
DISABLE—Disables auto bias. 
ENABLE—Enables auto bias. 
SP TRACK 
 
SETPOINT TRACKING—The local setpoint can be 
configured to track either PV or RSP as listed below. 
Not configurable when Auto Bias is set.  
 ATTENTION   For selections other than NONE, 
LSP is stored in nonvolatile memory only when there 
is a mode change; i.e., when switching from RSP to 
LSP or from Manual to Automatic. If power is lost, 
then the current LSP value is also lost. 
 
NONE 
NO TRACKING—If local setpoint tracking is not 
configured, the LSP will not be altered when transfer 
from RSP to LSP is made. 
 
PV 
PV—Local setpoint tracks the PV when in manual. 
 
RSP 
RSP—Local setpoint tracks remote setpoint when in 
automatic. When the controller transfers out of 
remote setpoint, the last value of the remote setpoint 
(RSP) is inserted into the local setpoint. 
PWR MODE 
 
POWER UP CONTROLLER MODE RECALL—This 
selection determines which mode and setpoint the 
controller will use when the controller restarts after a 
power loss. 
 
MANUAL 
MANUAL, LSP—At power-up, the controller will use 
manual mode with the local setpoint displayed. 
 
A LSP 
AUTOMATIC MODE, LAST LSP—At power-up, the 
controller will use automatic mode with the last local 
setpoint used before power down displayed. 
12/04  UDC3200 Universal Digital Controller Product Manual  73