Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
LOW VAL 
Low Scale Value within 
the range of the selected 
variable to represent the 
minimun output (0 or 4 
mA) 
AUXILIARY OUTPUT LOW SCALING FACTOR— 
This is a value in engineering units used to 
represent all AUX OUT parameters except Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %.  However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
HIGH VAL 
High Scale Value within 
the range of the selected 
variable to represent the 
maximum output (20 mA) 
AUXILIARY OUTPUT HIGH SCALING FACTOR— 
This is a value in engineering units used to 
represent all AUX OUT parameters except Output. 
For Output, this is a value in percent and can be any 
value between –5 % and +105 %.  However, keep in 
mind that relay output types can only be scaled 0 % 
to 100 %. 
DIG INP1 
 
DIGITAL INPUT 1 SELECTIONS—All selections are 
available for Input 1. The controller returns to its 
original state when contact opens, except when 
overruled by the keyboard. 
 
 
NONE 
NO DIGITAL INPUT SELECTIONS 
  TO MAN 
TO MANUAL—Contact closure puts the affected 
loop into manual mode. Contact open returns 
controller to former mode. 
  TO LSP 
TO LOCAL SETPOINT—When a remote setpoint is 
configured, contact closure puts the controller into 
local setpoint 1. When contact opens, the controller 
returns to former operation—local or remote 
setpoint—unless SP Select key is pressed while 
digital input is active. If this happens, the controller 
will stay in the local setpoint mode when contact 
opens. 
  TO 2SP 
TO LOCAL SETPOINT TWO—Contact closure puts 
the controller into local setpoint 2. 
 
TO 3SP 
TO LOCAL SETPOINT THREE—Contact closure 
puts the controller into local setpoint 3. 
 
TO DIR 
TO DIRECT ACTION—Contact closure selects 
direct controller action. 
80  UDC3200 Universal Digital Controller Product Manual  12/04