EasyManua.ls Logo

IMO HD2-3.7A-43 - 9.4.5.2 Description of other Modbus function addresses; 9.4.6 Fieldbus scale

IMO HD2-3.7A-43
408 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HD2 Series Inverter Communication
-307-
1# 2 # 3 # 4 # 32 #
120Ω
120Ω
Figure 9-2 On-site chrysanthemum connection diagram
1# 2# 3# 31#Master
A+
B-
A+ B-
Figure 9-3 Simplified chrysanthemum connection diagram
IMO
VFD
Address 1
Earth
485+
485-
485+
485-
485+
485-
120Ω
Terminal resistor
PC
Converter
GND
RS232-RS485
Max. length of the
cable: 15 m
Shielded twisted pair
Address 2 Address N
IMO
VFD
IMO
VFD
Earth Earth
Figure 9-4 Practical application diagram of chrysanthemum connection
Figure 9-5 shows the start connection diagram. When this connection mode is adopted, the two
devices that are farthest away from each other on the line must be connected with a terminal resistor
(in Figure 9-5, the two devices are devices 1# and 15#).
1#
15#
32#
6
#
Main control
device
Figure 9-5 Star connection
Use shielded cable, if possible, in multi-device connection. The baud rates, data bit check settings,
and other basic parameters of all the devices on the RS485 line must be set consistently, and

Table of Contents

Related product manuals