HD2 Series Inverter Basic Operation Guidelines
-50-
Current running
command channel
P00.01
Multi-function
terminal function (36)
Command switches
to keypad
Multi-function terminal
function (37)
Command switches to
terminal
Multi-function terminal
function (38)
Command switches to
communication
Note: "/" means this multi-function terminal is invalid under current reference channel.
Related parameter list:
0: Sensorless vector control (SVC) mode 0
1: SVC 1
2: Space voltage vector control mode
3: FVC
Note: To select 0, 1, or 3 as the control
mode, enable the inverter to perform motor
parameter autotuning first
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
Communication mode of
running commands
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET/EtherNet IP
4: Programmable card
5: Bluetooth card
6: Reserved
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1; carry out
comprehensive motor parameter autotuning;
rotary autotuning is used in cases where high
control precision is required.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load.
3: Static autotuning 2 (partial autotuning);