4 Instructions4.5.3 Table Operation
Before sorting
Row Number
Column Number
1 2 3
1
S S+1 S+2
1 2 8
2
S+3 S+4 S+5
2 6 7
3
S+6 S+7 S+8
3 4 3
Table data after sorted in ascending order based on the second column
Row Number
Column Number
1 2 3
1
D D+1 D+2
1 2 8
2
D+3 D+4 D+5
3 4 3
3
D+6 D+7 D+8
2 6 7
Note:
The operands cannot be modied when the SORT2 instruction is executed.
Switch the ow from OFF to ON before you execute the instruction for the second time.
Keep the operands and data unchanged during execution.
The contents of S and D can overlap completely or be staggered, but they cannot overlap partially.
The 32-bit instruction is used in the same way as the 16-bit instruction. The operands occupy two 16-
bit elements.
An operation error occurs in the following conditions. The error ag M8067 is set to ON to identify this error
and the error code is stored in D8067.
1. Error K6705 is returned when the value in S or D is out of range.
2. Error K6706 is returned when the value of m1, m2, or n is out of range.