B.5 System Error Code D8064
722
Appendix
Error Code Content
D8063 Communication error
6310 Reserved
6311 Reserved
6312 Incorrect parallel control (1:1) protocol character
6313 Incorrect parallel control (1:1) protocol sum
6314 Incorrect parallel control (1:1) protocol format
6315 Parallel control (1:1) protocol communication timeout
6316-6329 Reserved
6330+10*X Incorrect Modbus slave station address, larger than 247
6331+10*X Data frame length incorrect, nonconforming, or smaller than 5
6332+10*X
Incorrect address, standard error frame, or inconsistent sending/receipt
address
6333+10*X CRC error
6334+10*X
Unsupported instruction code, standard error frame, inconsistent data
sending/receiving command, or unsupported command
6335+10*X Receiving timeout
6336+10*X Data error, standard error frame
6337+10*X Buffer overow (none)
6338+10*X Frame error, standard error frame
6339+10*X
Incorrect serial protocol: failure to congure the correct protocol during
execution of the Modbus or RS instruction
6380-6399: CAN communication error code
6380 Sending timeout
6381 Receiving timeout
6382 CAN transmitting busy
6383 CAN receiving busy
6384-6399 Reserved
16300-16319 Ethernet communication error code
16300-16311 Reserved
16312 Protocol identier error, Modbus protocol
16313 Frame length error
16314 Frame timeout
16315 Frame not identied by slave station (for master station only)
16316 Invalid IP address
16317-16319 Reserved
16320-16339 Extension module communication error code
16340-16359 USB communication error code
16360-16379 Control panel and interface communication error code
16380-16399 Reserved
26300-26399 Reserved
B.5 System Error Code D8064
Error Code Content
D8064 Incorrect system parameter
6401 Program-parameter inconsistency
6402 Incorrect program capacity setting
6403
Incorrect setting of changeable power failure retentive area of soft
elements

Table of Contents