3 Elements3.2 Input/Output Relay
Name Description
For special purpose (16-bit) SD0 to SD1023
1024
points
Retained upon power failure
For address indexing (16-bit) V0 to V7, 0 to Z7 16 points Retained upon power failure
File register
Extended register (16-bit) R0 to R32767
32,768
points
Retained upon power failure
Marker
For the CJ instruction P0 to P511 512 points Used in combination with the LBL instruction
Subprogram
For the CALL instruction / 512 points
Congurable as a general subprogram, an encrypted
subprogram, a subprogram with parameters, or an
encrypted subprogram with parameters
Output interrupts X000 to X007
I00 □ , I10 □ , I20
, I30 □ , I40 □ ,
I50 □ , I56 □ , I57
8 points
□ 0 indicates a falling edge interrupt, and 1 indicates
a rising edge interrupt.
When the edge interrupt disabling ag bit register
is set to ON, the corresponding input interrupt is
disabled.
Timing interrupt I6 □□ to I8 □□ 3 points □□ = 01 to 99, and time base = 1 ms
Counting completion interrupt I010 to I080 8 points For the DHSCS instruction
Pulse completion interrupt I502 to I506 5 points
Motion control subprogram MC00 to MC63 64
G-code subprogram CNC00 1
Corresponding to the MC10000. Each G-code
subprogram supports up to 16 Oxxxx subprograms.
Nested pointer
For the main control loop N0 to N7 8 points For the MC instruction
Constant
Decimal constant K
16-bit -32,768 to +32,767
32-bit -2,147,483,648 to +2,147,483,647
Hexadecimal constant H
16-bit 0 to FFFF
32-bit 0 to FFFFFFFF
Real number E 32-bit 0, -1.0*2e128 to -1.0*2e-126, 1.0*2e-126 to 1.0*2e128 (32-bit)
3.2 Input/Output Relay
3.2.1 Input Relay X
The input relay X is a PLC external input signal status element that uses the X port to detect the status of
an external signal. 0 indicates an open-circuit external signal (OFF) and 1 indicates a closed external signal
(ON).
The input relay status cannot be modied using a project instruction, and the contact signals (normally ON
or normally OFF) can be used innitely in the user project.
Relay signals are marked with X0, X1, X7, X10, and X11, and numbered with an octal number.
When a local extension module is connected, the X ports on the extension module are numbered
immediately after the X ports on the main module. For example, if the main module is the H3U standard
model, when an AM600-1600END extension module is connected, because the last X port of the main
module is X37, the X ports of the extension module are numbered X40 to X47, and X50 to X57 during
programming.