A.3 M8000 Flag and D8000 Register
712
Appendix
M
Element
Description
D
Element
Description
M8190 N:N data transmission slave station 7 error D8190 Z5 register
M8191 N:N data - transmitting D8191 V5 register
M8192
N:N protocol compatible with Mitsubishi
communication format
D8192 Z6 register
M8193 Reserved D8193 V6 register
M8194 Reserved D8194 Z7 register
M8195 C251 multiplication control D8195 V7 register
M8196 C252 multiplication control D8196 Reserved
M8197 C253 multiplication control D8197 Reserved
M8198 C254 multiplication control D8198
CANlink remote device identier (10224 for H2U and
10226 for H1U)
M8199 C255 multiplication control D8199 Reserved
Counter increment/decrement or control Serial port communication link
M8200 C200 control D8200
Auxiliary board program version, 0xBxxx, in
hexadecimal format
M8201 C201 control D8201
Current N:N and N:N extensible communication
connection scan time
M8202 C202 control D8202
Maximum N:N and N:N extensible communication
connection time
M8203 C203 control D8203 Number of N:N master station communication errors
M8204 C204 control D8204 Number of N:N slave station 1 communication errors
M8205 C205 control D8205 Number of N:N slave station 2 communication errors
M8206 C206 control D8206 Number of N:N slave station 3 communication errors
M8207 C207 control D8207 Number of N:N slave station 4 communication errors
M8208 C208 control D8208 Number of N:N slave station 5 communication errors
M8209 C209 control D8209 Number of N:N slave station 6 communication errors
M8210 C210 control D8210 Number of N:N slave station 7 communication errors
M8211 C211 control D8211
N:N master station communication error code
Number of N:N extensible protocol slave station 8
communication errors
M8212 C212 control D8212
N:N slave station 1 communication error code
Number of N:N extensible protocol slave station 9
communication errors
M8213 C213 control D8213
N:N slave station 2 communication error code
Number of N:N extensible protocol slave station 10
communication errors
M8214 C214 control D8214
N:N slave station 3 communication error code
Number of N:N extensible protocol slave station 11
communication errors
M8215 C215 control D8215
N:N slave station 4 communication error code
Number of N:N extensible protocol slave station 12
communication errors
M8216 C216 control D8216
N:N slave station 5 communication error code
Number of N:N extensible protocol slave station 13
communication errors
M8217 C217 control D8217
N:N slave station 6 communication error code
Number of N:N extensible protocol slave station 14
communication errors
M8218 C218 control D8218
N:N slave station 7 communication error code
Number of N:N extensible protocol slave station 15
communication errors

Table of Contents