EasyManua.ls Logo

Inovance H3U Series - Page 90

Inovance H3U Series
737 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
4
4 Instructions 4.3.1 Contact Comparison
AND#: AND contact status bit operation
Overview
Whether the AND# instruction is enabled is determined based on the bit logical operation result (a node
connected to another node in series).
AND# S1 S2
AND contact
status bit
operation
Applicable model:
H3U
S1 Data 1 Element number of source data 1
16-bit instruction (5
steps)
AND#: Continuous
execution
32-bit instruction (9
steps)
ANDD#:
Continuous
execution
S2 Data 2 Element number of source data 2
Note: The # comparison operator can be &, |, or ^.
Operands
Operand
Bit Element Word Element
System·User System·User Bit Designation Indexed Address Constant
Real
Number
S1 X Y M T C S SM D R T C SD KnX KnY KnM KnS KnSM
V,Z
Modication K H E
S2 X Y M T C S SM D R T C SD KnX KnY KnM KnS KnSM
V,Z
Modication K H E
Note: The elements in gray background are supported.
Function
A logical operation (AND: &; NOT: |; XOR: ^) is performed on [S1] and [S2]. The instruction is enabled if the
operation result is not 0; if the operation result is 0, the instruction is disabled. The execution results are as
follows:
16-bit Instruction 32-bit Instruction
Enabled State
Condition
Disabled State
Condition
AND& ANDD& S1&S2 ≠ 0 S1&S2 = 0
AND| ANDD| S1|S2 ≠ 0 S1|S2 = 0
AND^ ANDD^ S1^S2 ≠ 0 S1^S2 = 0
Application

Table of Contents

Other manuals for Inovance H3U Series

Related product manuals