Section E - Hydraulics
Pressure Testing
Power Management System (P.M.S.)
E - 63 E - 63
9803-9450-2
Power Management System (P.M.S.)
Calibration Procedure
It is necessary to do this procedure if you have fitted a new
P.MS. controller (E.C.U. 4)
1 Make sure that the hydraulic fluid is at correct working
temperature (50 °C, 122 °F).
2 Remove the seat and seat base.
Fig 51.
3 Connect a 0 - 40 bar (0 - 600 lb/in
2
) pressure gauge
to test connector A.
Fig 52.
4 Remove fuse and relay cover. Remove blanking plug
from connector B (fed by wire numbers 144A and
508). Connect test button C (part number 701/80490)
into the harness as shown.
Note: The next step is for non High Flow machines that do
not have sensitivity control F K
Fig 53. ( T E-64). If you
need to fit this control as a permanent fixture K
To fit
Sensitivity Control to Non High Flow
Machines ( T E-66)
A
C
B