recommend that you not mix DIP switch sengs in your system. See Table 11 on page 40 for
informaon about the input and output voltages when you use the DIP switches.
The JNP10K-PWR-AC2 power supply has internal fans that contribute to chassis cooling. Consequently,
all three power supplies must be present in a running chassis to provide adequate airow. While all
power supplies are required to be present in the chassis, they do not all need to be connected to power.
If a power supply is installed in a slot but not connected to a power source, it draws power from the
chassis to power the internal fans in the power supplies.
Figure 19: JNP10K-PWR-AC2 Power Supply
WARNING: Extreme burn danger! Do not handle an HVAC or HVDC power supply
running in the chassis without heat-protecve gloves, such as welder’s gloves. The
JNP10K-PWR-AC2 can reach temperatures in the range of 158° F to 176° F (70° C to
80° C) under running condions.
WARNING: The router is pluggable type A equipment installed in a restricted-access
locaon. It has a separate protecve earthing terminal on the chassis that must be
connected to earth ground permanently to ground the chassis adequately and protect
the operator from electrical hazards.
CAUTION: Before you begin installing the router, ensure that a licensed electrician has
aached an appropriate grounding lug to the grounding cable that you supply. Using a
grounding cable with an incorrectly aached lug can damage the router.
39