CAUTION: Use a 2-pole circuit breaker rated at 25 A in the building installaon and the
system, or according to the local electrical code.
Table 11: DIP Switch Sengs for JNP10K-PWR-AC2 Power Supplies
INP0 (Switch 1) INP1 (Switch 2) H/L (High Input 30 A/
Low Input 20 A)
Output Power
On On On (30 A) 5500 W
On On O (20 A) 3000 W
On O On (30 A) 5000 W
O On On (30 A) 5000 W
On O O (20 A) 2700 W
O On O (20 A) 2700 W
CAUTION: It is important to connect both input feeds of the JNP10K-PWR-AC2 power
supply to the main AC power before loading the system with power.
JNP10K-PWR-AC2 Power Specicaons
The JNP10K-PWR-AC2 power supply supports AC, high-voltage alternang current (HVAC) and high-
voltage direct current (HVDC).
Table 12 on page 41 lists the power specicaons for the AC power supply (JNP10K-PWR-AC2) used
in an MX10004 chassis.