MX10004 Power Cable Specicaons
IN THIS SECTION
JNP10K-PWR-AC2 Power Cable Specicaons | 44
JNP10K-PWR-AC2 Power Cable Specicaons for 30-A Input | 47
Most sites distribute power through a main conduit that leads to frame-mounted power distribuon
panels, one of which can be located at the top of the rack that houses the router. An AC power cord
connects each power supply to the power distribuon panel.
NOTE: In North America, AC power cords must not exceed 15 feet (approximately 4.5 meters) in
length, to comply with Naonal Electrical Code (NEC) Secons 400-8 (NFPA 75, 5-2.2) and
210-52 and with Canadian Electrical Code (CEC) Secon 4-010(3). The cords shipped with the
router to North America and Canada are in compliance.
The MX10004 AC, high-voltage alternang current (HVAC), and high-voltage direct current (HVDC)
power supplies have specic cord requirements. Use the following secons to determine the cable
requirements based on the model of your power supply and any mode sengs:
• For JNP10K-PWR-AC2 with 20-A input, see "JNP10K-PWR-AC2 Power Cable Specicaons" on
page 44.
• For JNP10K-PWR-AC2 with 30-A input, see "JNP10K-PWR-AC2 Power Cable Specicaons for 30-
A Input" on page 47.
JNP10K-PWR-AC2 Power Cable Specicaons
The JNP10K-PWR-AC2 power supply operates in two modes:
• 20-A input with 3000-W output; see Table 16 on page 45 for a list of appropriate cables.
• 30-A input with 5500-W output; see "JNP10K-PWR-AC2 Power Cable Specicaons for 30-A Input"
on page 47 for a list of appropriate cables and connectors for 30-A input.
WARNING: Do not run JNP10K-PWR-AC2 power supplies using 16-A or 20-A cables if
connected to 30-A input.