Table 29: MX10004 Environmental Tolerances
Descripon Tolerance
Altude No performance degradaon up to 6000 feet (1829 meters).
Relave humidity
Normal operaon ensured in a relave humidity range of 5%
through 90%, noncondensing.
Short-term operaon ensured in a relave humidity range of 5%
through 93%, noncondensing.
NOTE: As dened in NEBS GR-63-CORE, Issue 3: Short-term refers
to a period of not more than 96 consecuve hours (four days) and
not more than 360 hours (15 days) in 1 year.
Temperature
Normal operaon ensured in temperature range of 32° F through
104° F (0° C through 40° C).
Nonoperang storage temperature in shipping container: -40° F
through 158° F (-40° C through 70° C).
Short-term operaon ensured in temperature range of 32° F
through 131° F (0° C through 55° C) at 6000 altude.
NOTE: As dened in NEBS GR-63-CORE, Issue 3: Short-term refers
to a period of not more than 96 consecuve hours (four days) and
not more than 360 hours (15 days) in 1 year.
NOTE: Short-term operaon is applicable only to MX10K-LC480
line card in the MX10004 chassis.
Seismic zone Designed to comply with Zone 4 earthquake requirements according to
NEBS GR-63-CORE, Issue 3.
NOTE: Install MX10004 routers only in restricted-access areas, such as dedicated equipment
rooms and equipment closets. Install routers in accordance with Arcles 110-16, 110-17, and
110-18 of the Naonal Electrical Code, ANSI/NFPA 70.