When using multiple servo drives, do not connect the ground wires of multiple drives in series, and
use a single-point grounding method;
⚫
The drive should be grounded with the shortest and thickest possible cable (>2mm²). If the
ground wire is long, the diameter of the ground wire should be increased (≥4mm²) to ensure
that the grounding resistance is less than 100Ω
;