Step 4: Save and reboot
See Chapter 5
Step 5: Start operation
Start operation via DIN or PC software.
6.2 Velocity mode (-3, 3)
There are 2 kinds of velocity mode: -3 and 3. The velocity command can be specified via Target_Speed or analog
input (analog speed mode), or via digital input (DIN speed mode
).
Table 6-7 Description of velocity mode’s parameters
-3: The velocity command is specified directly
by Target_Speed. Only the velocity control
loop is active.
3: The velocity command is specified by
Target_Speed with profile acceleration and
profile deceleration. Velocity- and position
control loops are active.
Speed
position
direction
control
run polarity reversal
0: Counterclockwise is the positive
direction (default value)
1: Clockwise is the positive direction
Attention
The DIN function has highest priority – the object value can not be modified manually
anymore if it’s configured in DIN, e.g. if the enable function is configured,
Controlword(6040.00) cannot be modified manually via PC software
.
Attention
When the value directly written in the Operation_mode through the basic operation
interface cannot be saved after power off and restart, the Operation_mode can be
saved by configuring the Operation_mode control function on the input port of the
drive, but it should be noted that the Operation_mode is selected 0 first. Set it with the
value of operation mode selection 1, and then store the control parameters.
Attention
The speed position direction control cannot be modified in the enabled state.