Parameterisaon required
1.
Set the operang mode "MS: Torque mode [-1]" in 0x6060 (P301.00).
2.
Set the rated motor torque in 0x6076 (P325.00).
3.
Set the permissible maximum torque in 0x6072 (P326.00).
The seng is made in percent with reference to the rated motor torque set in 0x6076
(P325.00).
4.
Select the source for the posive torque limit in 0x2949:001 (P337.01).
Default seng: Maximum torque 0x6072 (P326.00)
In case of selecon "Analog Input 1 [2]": Set seng range in 0x2636:011 (P430.11) and
0x2636:012 (P430.12).
In case of selecon "Analog Input 2 [3]": Set seng range in 0x2637:011 (P431.11) and
0x2637:012 (P431.12).
In case of selecon "Posive torque limit [4]": Set the posive torque limit in 0x60E0.
5.
Select the source for the negave torque limit in 0x2949:002 (P337.02).
Default seng: (-) Maximum torque 0x6072 (P326.00)
In case of selecon "Analog Input 1 [2]": Set seng range in 0x2636:011 (P430.11) and
0x2636:012 (P430.12).
In case of selecon "Analog Input 2 [3]": Set seng range in 0x2637:011 (P431.11) and
0x2637:012 (P431.12).
In case of selecon "Negave torque limit [4]": Set the negave torque limit in 0x60E1.
6.
Select the source for the upper speed limit in 0x2946:003 (P340.03).
Default seng: Maximum frequency 0x2916 (P211.00)
In case of selecon "Analog input 1 [2]": Set seng range in 0x2636:002 (P430.02) and
0x2636:003 (P430.03).
In case of selecon "Analog input 2 [3]": Set seng range in 0x2637:002 (P431.02) and
0x2637:003 (P431.03).
In case of selecon "Upper frequency limit [4]": Set the upper speed limit in [Hz] in
0x2946:005 (P340.05).
In case of selecon "Upper speed limit [5]": Set the upper speed limit in [vel. unit in
0x2946:001 (P340.01).
7.
Select the source for the lower speed limit in 0x2946:004 (P340.04).
Default seng: (-) Maximum frequency 0x2916 (P211.00)
In case of selecon "Analog input 1 [2]": Set seng range in 0x2636:002 (P430.02) and
0x2636:003 (P430.03).
In case of selecon "Analog input 2 [3]": Set seng range in 0x2637:002 (P431.02) and
0x2637:003 (P431.03).
In case of selecon "Lower frequency limit [4]": Set the lower speed limit in [Hz] in
0x2946:006 (P340.06).
In case of selecon "Lower speed limit [5]": Set the lower speed limit in [vel. unit in
0x2946:002 (P340.02).
8.
Select the standard setpoint source for the torque control in 0x2860:003 (P201.03).
Default seng: Analog input 1. In case of this selecon, set the seng range in
0x2636:011 (P430.11) and 0x2636:012 (P430.12).
In case of selecon "Analog input 2 [3]": Set seng range in 0x2637:011 (P431.11) and
0x2637:012 (P431.12).
Except for the network, the torque setpoint must be given in percent with regard to the
0x6076 (P325.00) rated motor torque.
Via the network the torque setpoint is selected via the mappable parameter 0x400B:
008 (P592.08) in [Nm / 2
scaling factor
]. The scaling factor can be set in 0x400B:009
(P592.09).
9.
Oponally: For a "smooth" change-over between dierent setpoint sources, adapt the
ramp me for the torque setpoint in 0x2948:002 (P336.02).
The torque control with frequency limitaon is now acve and the inverter responds to the
torque setpoint given by the selected setpoint source.
Motor control
Opmisaon of the control loops
Motor controller sengs
207