EasyManua.ls Logo

Lenze i55AE155F

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.7.8 Parameter data transfer
The acyclic/non-cyclic data access (service access) provides a procedure for the PLC (scan-
ner) to access any drive or device parameter.
This type of parameter access is typically used for ...
monitoring or the not me-controlled parameter access with low priority;
wring parameter data (assembly data) for controlling the inverter (adapter).
For this purpose, the device supports several methods.
Explicit Messaging
An explicit message is a logic instrucon in the PLC program for the message transfer. It can be
used to read or write a parameter seng or the data of an EtherNet/IP node (assembly data).
If the Allen-Bradley control systems»CompactLogix™«, »ControlLogix®« and »SoLogix™« are
used, the "Explicit Message" instrucon provides the funconalies described in the following
secons. Further PLC types can be found in the programming documentaon of the PLC.
General drive variables (parameters and subindices) are contained in class "0x6E". The
instance is the index number of the parameter and the aribute is the subindex number. If no
subindex is available, the aribute must be set to "0". The aribute value "1" is only suppor-
ted for those clients that do not support the aribute value "0".
All these variables have the data type SINT (8 bit, 1-byte objects), INT (16 bit, 2-byte objects)
or DINT (32 bit, 4-byte objects).
The device parameters and the PLC program variables must have the same data lengths!
Conguring the network
EtherNet/IP
Parameter data transfer
342

Table of Contents

Related product manuals