EasyManua.ls Logo

Lenze i55AE155F

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.2.2 Process controller rinse funcon
This funcon accelerates the motor in idle state of the process controller at regular intervals
to a dened speed.
Details
A typical applicaon for this funcon is the rinsing of a pipe system with a pump that has been
in an inacve state for a longer period to prevent deposits.
In order to acvate the rinsing funcon, set the selecon "Enabled [1]" in 0x4024:001
(P615.01).
The following diagram demonstrates the funcon:
0 Hz
t
0x4024:002 0x4024:004 0x4024:002 0x4024:004
0x4024:003
Output frequency
The rinsing funcon uses the ramp mes set for the "MS: Velocity mode". 4Frequency
limits and ramp mes ^ 156
Parameter Name / value range / [default seng] Info
0x4024:001
(P615.01)
Automac rinsing: Rinsing in idle state
(Auto-rinsing: Rinsing in idle)
1 = acvate automac rinsing in idle state.
0 Inhibited
1 Enabled
0x4024:002
(P615.02)
Automac rinsing: Rinse interval
(Auto-rinsing: Rinse interval)
0.0 ... [30.0] ... 6000.0 min
Time interval between two rinsing processes.
0x4024:003
(P615.03)
Automac rinsing: Rinse speed
(Auto-rinsing: Rinse speed)
-599.0 ... [0.0] ... 599.0 Hz
Speed setpoint for rinse funcon.
0x4024:004
(P615.04)
Automac rinsing: Rinse period
(Auto-rinsing: Rinse period)
0.0 ... [0.0] ... 6000.0 s
Duraon of a rinsing process.
Conguring the process controller
Process controller - idle state and rinse funcon
Process controller rinse funcon
416

Table of Contents