9.6.13 Error codes for parameter data transfer
The following table lists all possible error codes for the acyclic data exchange:
Error code Descripon Explanaon Addional infor-
maon
0x0000 Parameter number impermissible Access to non-available parameter. -
0x0001 Parameter value cannot be changed Change access to a parameter value that cannot be
changed.
Subindex
0x0002 Lower or upper value limit exceeded Change access with value beyond the value limits. Subindex
0x0003 Subindex impermissible Access to non-available subindex. Subindex
0x0004 No array Access with subindex to non-indicated parameter. -
0x0005 Incorrect data type Change access with value that does not match the
data type of the parameter.
-
0x0006 No seng permied (only reseable) Change access with a non-zero value where it is not
permied.
Subindex
0x0007 Descripon element cannot be changed Change access to a descripon element that cannot
be changed.
Subindex
0x0008 Reserved (PROFIdrive prole V2: PPO-Write requested in IR is
not available.)
-
0x0009 Descripon data not available Access to non-available descripon (parameter value
is available).
-
0x000A Reserved (PROFIdrive prole V2: Wrong access group.) -
0x000B No parameter change rights Change access with missing parameter change rights. -
0x000C Reserved (PROFIdrive prole V2: Wrong password.) -
0x000D Reserved (PROFIdrive prole V2: Text cannot be read in cyclic
data transfer.)
-
0x000E Reserved (PROFIdrive prole V2: Name cannot be read in cyclic
data transfer.)
-
0x000F No text array available Access to non-available text array (parameter value is
available).
-
0x0010 Reserved (PROFIdrive prole V2: No PPO-Write.) -
0x0011 Request cannot be executed due to the operang
state
Access is not possible for temporary reasons that are
not specied in detail.
-
0x0012 Reserved (PROFIdrive prole V2: Other error.) -
0x0013 Reserved (PROFIdrive prole V2: Date cannot be read in cyclic
data transfer.)
-
0x0014 Value impermissible Change access with the value that is within the value
limits but that is impermissible for other permanent
reasons (parameters with dened individual values).
Subindex
0x0015 Response too long The length of the current response exceeds the maxi-
mum length transferrable.
-
0x0016 Parameter address impermissible Impermissible value or value which is not supported
for the aribute, number of subindexes, parameter
number, or subindex, or a combinaon.
-
0x0017 Format impermissible Write request: Impermissible or non-supported for-
mat of parameter data.
-
0x0018 Number of values not consistent Write request: Number of parameter data values does
not match the number of subindexes in the parameter
address.
-
0x0019 Axis impermissible Access to non-available axis. For double axis, only
0x00 or 0x01 permied.
-
0x001A Reserved - -
...
0x00FF