9.6.13 Error codes for parameter data transfer
The following table lists all possible error codes for the acyclic data exchange:
Error code Descripon Explanaon Addional infor-
maon
0x0000 Parameter number impermissible Access to non-available parameter. -
0x0001 Parameter value cannot be changed Change access to a parameter value that cannot be
changed.
Subindex
0x0002 Lower or upper value limit exceeded Change access with value beyond the value limits. Subindex
0x0003 Subindex impermissible Access to non-available subindex. Subindex
0x0004 No array Access with subindex to non-indicated parameter. -
0x0005 Incorrect data type Change access with value that does not match the
data type of the parameter.
-
0x0006 No seng permied (only reseable) Change access with a non-zero value where it is not
permied.
Subindex
0x0007 Descripon element cannot be changed Change access to a descripon element that cannot
be changed.
Subindex
0x0008 Reserved (PROFIdrive prole V2: PPO-Write requested in IR is
not available.)
-
0x0009 Descripon data not available Access to non-available descripon (parameter value
is available).
-
0x000A Reserved (PROFIdrive prole V2: Wrong access group.) -
0x000B No parameter change rights Change access with missing parameter change rights. -
0x000C Reserved (PROFIdrive prole V2: Wrong password.) -
0x000D Reserved (PROFIdrive prole V2: Text cannot be read in cyclic
data transfer.)
-
0x000E Reserved (PROFIdrive prole V2: Name cannot be read in cyclic
data transfer.)
-
0x000F No text array available Access to non-available text array (parameter value is
available).
-
0x0010 Reserved (PROFIdrive prole V2: No PPO-Write.) -
0x0011 Request cannot be executed due to the operang
state
Access is not possible for temporary reasons that are
not specied in detail.
-
0x0012 Reserved (PROFIdrive prole V2: Other error.) -
0x0013 Reserved (PROFIdrive prole V2: Date cannot be read in cyclic
data transfer.)
-
0x0014 Value impermissible Change access with the value that is within the value
limits but that is impermissible for other permanent
reasons (parameters with dened individual values).
Subindex
0x0015 Response too long The length of the current response exceeds the maxi-
mum length transferrable.
-
0x0016 Parameter address impermissible Impermissible value or value which is not supported
for the aribute, number of subindexes, parameter
number, or subindex, or a combinaon.
-
0x0017 Format impermissible Write request: Impermissible or non-supported for-
mat of parameter data.
-
0x0018 Number of values not consistent Write request: Number of parameter data values does
not match the number of subindexes in the parameter
address.
-
0x0019 Axis impermissible Access to non-available axis. For double axis, only
0x00 or 0x01 permied.
-
0x001A Reserved - -
...