4.2.1.2 Fusing and terminal data
Fuse data
Inverter I55AE125A
I55AE137A
I55AE175A
I55AE211A
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 16 25
Circuit breaker
Characteriscs B
Max. rated current A 16 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 16 25
Circuit breaker
Characteriscs B
Max. rated current A 16 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
Fuse data
Inverter I55AE125A
I55AE137A
I55AE175A
I55AE211A
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 30
Circuit breaker
Characteriscs -
Max. rated current A 15 30
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 30
Circuit breaker
Characteriscs -
Max. rated current A 15 30
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
Electrical installaon
Mains connecon
1-phase mains connecon 120 V
30