Variable mapping
Via 0x232B:001 ... 0x232B:024 (P530.01 ... 24), 24 registers can be mapped to parameters
of the inverter.
Format: 0xiiiiss00 (iiii = index hexadecimal, ss = subindex hexadecimal)
The display of the internal Modbus register numbers in 0x232C:001 ... 0x232C:024
(P531.01 ... 24) is generated automacally. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in 0x232D (P532.00). The user can read this "validaon code" and
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is congured correctly for the respecve applicaon.
Parameter Name / value range / [default seng] Info
0x232B:001 ...
0x232B:024
(P530.01 ... 24)
Modbus parameter mapping: Parameter 1 ... Parame-
ter 24
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entries for Modbus register 40103 ... 40149.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
0x232C:001 ...
0x232C:024
(P531.01 ... 24)
Modbus register assignment: Register 1 ... Register 24
(Reg. assigned: Register 1 ... Register 24)
Read only
Display of the internal Modbus register number starng from which the
parameter mapped in 0x232B:001 ... 0x232B:024 (P530.01 ... 24) is
stored.
For the rst parameter mapped, always 2500.
From the second parameter mapped, 2500 + oset. The oset results
from the data types of the previously mapped parameters.
0x232D
(P532.00)
Modbus vericaon code
(Vericaoncode)
Read only
9.5.9 LED status displays
Informaon about the Modbus status can be obtained quickly via the "MOD-RUN" and "MOD-
ERR" LED displays on the front of the inverter.
The meaning can be seen from the tables below.
Inverter not acve on the Modbus bus (yet)
LED "MOD-RUN" LED "MOD-ERR" Meaning
o on
Internal error
Both LEDs are ickering alternately
Automac detecon of baud rate and data format acve.
Inverter acve on the Modbus
The green "MOD-RUN" LED indicates the communicaon status:
LED "MOD-RUN" Communicaon status
o No recepon / no transmission
on
Recepon / transmission acve
The red "MOD-ERR" LED indicates an error:
LED "MOD-ERR" Error
o No fault
Blinking
Communicaon error
Conguring the network
Modbus RTU
LED status displays
290