14.2.3 Example 3: Run forward/Run reverse/stop (status-controlled)
The "Run" funcon automacally becomes a "start enable" if the funcons "Run
forward (CW)"/"Run reverse (CCW)" are connected to triggers.
This example shows a status-controlled start/stop via three switches:
•
Switch S1 enables the start. Without start enable, the motor cannot be started.
•
Switch S2 starts the motor in forward direcon of rotaon.
•
Switch S3 starts the motor in backward direcon of rotaon.
•
The motor is stopped by cancelling the run commands (switches S2 and S3 open) or by
cancelling the start enable (switch S1 open).
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Start enable
Switch S2 Run forward (CW)
Switch S3 Run reverse (CCW)
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:008 (P400.08) Run forward (CW) Digital input 2 [12]
0x2631:009 (P400.09) Run reverse (CCW) Digital input 3 [13]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
Flexible I/O conguraon
Start / stop motor
Example 3: Run forward/Run reverse/stop (status-controlled)
540