6.2.3 Inverter diagnosīcs
The following parameters supply some informaīon about the current operaīng status of the
inverter.
This includes the following informaīon:
ā¢
Acīve access protecīon aīer log-in by means of PIN1/PIN2
ā¢
Currently loaded parameter seī«ngs
ā¢
Cause(s) for disable, quick stop and stop.
ā¢
Acīve control source and acīve setpoint source
ā¢
Acīve operaīng mode
ā¢
Keypad status
ā¢
Status of the internal motor control
Some of the following parameters contain bit-coded status words. Each single bit has a certain
meaning.
4Display of status words on keypad ^ 638
Parameter Name / value range / [default seī«ng] Info
0x2040
(P197.00)
Access protecīon status
(Protect. status)
ā¢
Read only
Bit-coded display of the acīve access protecīon aīer login by PIN1/
PIN2.
Bit 0 No write access
Bit 1 Only favorites changeable
0x2827
(P198.00)
Currently loaded parameter seī«ngs
(Status load. par)
ā¢
Read only
Display of the parameter seī«ngs currently loaded.
4Data handling ^ 141
4Saving/loading the parameter seī«ngs ^ 419
0 User seī«ngs User parameter seī«ngs of the memory module
1 Reset 60 Hz seī«ng Delivery status (default seī«ng) for 50-Hz device
2 Reset 50 Hz seī«ng Delivery status (default seī«ng) for 60-Hz device
3 OEM default seī«ngs OEM parameter seī«ngs of the memory module
0x282A:001
(P126.01)
Status words: Cause of disable
(Status words: Cause of disable)
ā¢
Read only
Bit-coded display of the cause(s) for disabled inverter.
Bit 0 Flexible I/O conī®guraīon 1 ā” the inverter was disabled by the trigger set in 0x2631:001 (P400.01).
Bit 1 Network 1 ā” the inverter was disabled via network.
Bit 2 Axis command 1 ā” the inverter was disabled via axis command .
Bit 6 Fault DC-bus 1 ā” the inverter was inhibited due to a DC-bus error.
Bit 7 Drive not ready 1 ā” the inverter was disabled internally since the drive was not ready for
operaīon.
Possible causes:
ā¢
Under/overvoltage in the DC bus
ā¢
Defect device hardware
Bit 8 Quick stop acīve 1 ā” the inverter has been disabled by the "Quick stop" funcīon.
Bit 9 Motor data idenīī®caīon 1 ā” the inverter was disabled by the "Automaīc idenīī®caīon of the
motor data" funcīon.
Bit 10 Automaīc holding brake control 1 ā” the inverter was disabled by the "Holding brake control" funcīon.
Bit 11 DC braking -
Bit 12 CiA402 Inverter disabled 1 ā” the inverter was disabled by the internal state machine.
The bit is only set if
ā¢
operaīng mode 0x6060 (P301.00) = "CiA: Velocity mode [2]" and
ā¢
state machine in the "Switch on disabled" state and
ā¢
the state change has not been carried out via the "Disable operaīon"
command.
Bit 13 CiA402 Quick stop opīon code 2 1 ā” the inverter has been disabled by the "Quick stop" funcīon.
Bit 14 Safe torque oī« (STO) 1 ā” the inverter has been disabled by the integrated safety system.
Bit 15 CiA402 operaīon mode 0 1 ā” the inverter has been disabled because the selecīon "No mode
change/no mode assigned [0]" is set in 0x6060 (P301.00).
Diagnosīcs and fault eliminaīon
Diagnosīcs parameter
Inverter diagnosīcs
114