15.4 3-phase mains connecon 230/240 V
15.4.1 Rated data
The output currents apply to these operang condions:
At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter I55AE125D I55AE137D I55AE155D I55AE175D I55AE211D I55AE215D I55AE222D
Rated power kW 0.25 0.37 0.55 0.75 1.1 1.5 2.2
Rated power hp 0.33 0.5 0.75 1 1.5 2 3
Mains voltage range 3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 V … 230 V/240 V
Rated mains current
without mains choke A 2.6 3.9 4.8 6.4 7.8 9.5 13.6
with mains choke A 2 3 3.8 5.1 5.6 6.8 9.8
Apparent output power kVA 0.6 0.9 1.2 1.6 2.2 2.6 3.6
Output current
2 kHz A - - 3.2 4.2 6 7 9.6
4 kHz A 1.7 2.4 3.2 4.2 6 7 9.6
8 kHz A 1.7 2.4 3.2 4.2 6 7 9.6
16 kHz A 1.1 1.6 2.1 2.8 4 4.7 6.4
Weight kg 0.8 1 1.35
Weight lb 1.8 2.2 3
Inverter I55AE240C I55AE255C
Rated power kW 4 5.5
Rated power hp 5 7.5
Mains voltage range 3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 V … 230 V/240 V
Rated mains current
without mains choke A 20.6 28.8
with mains choke A 15.7 21.9
Apparent output power kVA 6.4 8.7
Output current
2 kHz A 16.5 23
4 kHz A 16.5 23
8 kHz A 16.5 23
16 kHz A 11 15.3
Weight kg 2.1
Weight lb 4.6
Technical data
3-phase mains connecon 230/240 V
Rated data