EasyManua.ls Logo

Lenze i55AE155F

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.2.3.2 Fusing and terminal data
Fuse data
Inverter
I55AE125D
I55AE137D
I55AE155D
I55AE175D
I55AE211D
I55AE215D
I55AE222D
I55AE240C
I55AE255C
Cable installaon in compliance with EN 60204-1
Installaon method B2 C
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B -
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Fuse data
Inverter I55AE125D
I55AE137D
I55AE155D
I55AE175D
I55AE211D
I55AE215D
I55AE222D
I55AE240C
I55AE255C
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 / Class J, T, R
Max. rated current A 15 30 40
Circuit breaker
Characteriscs -
Max. rated current A 15 30 -
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 / Class J, T, R
Max. rated current A 15 30 40
Circuit breaker
Characteriscs -
Max. rated current A 15 30 -
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B -
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 230/240 V
39

Table of Contents