9.6.14 Restart communicaon
The following parameter can be used to restart or stop communicaon. Oponally it is also
possible to reset all communicaon parameters to the default status.
Details
A restart of communicaon is required aer changes of the interface conguraon (e. g. sta-
on address and baud rate) in order that the changed sengs become eecve.
For restarng communicaon, there are two opons:
a)
Switch inverter o and on again.
b)
Set the selecon = "Restart with current values [1]" in 0x2340.
Parameter Name / value range / [default seng] Info
0x2340 PROFIBUS communicaon
From version 03.00
Restart / stop communicaon.
0 No acon/no error Only status feedback
1 Restart with current values Restart communicaon with the current values.
2 Restart with default values Restart communicaon with the standard values of the communicaon
parameters.
5 Stop network communicaon Stop communicaon.
10 In progress Only status feedback
11 Acon cancelled
12 Error
Conguring the network
PROFIBUS
Restart communicaon
312

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals