11.11.2 "Automac" brake mode (automac operaon)
In automac operaon, the inverter automacally released the holding brake when the motor
is started. In the stopped state, the holding brake is closed.
DANGER!
Manual release of the holding brake
Also in automac operaon, a manual release of the holding brake is possible. The manually
triggered "Release holding brake" command has a direct impact on the "Release holding brake
[115]" trigger. Thus, the holding brake can be manually released if the power secon is
switched o.
The responsibility for a manual release of the holding brake has the external trigger source
for the "Release holding brake" command!
Precondions
Automac operaon is only available if the operang mode "MS: Velocity mode [-2]" or "MS:
Torque mode [-1]" is set in 0x6060 (P301.00).
Parameter Name / value range / [default seng] Info
0x6060
(P301.00)
Modes of operaon
(Modes of op.)
Seng can only be changed if the inverter is inhibi-
ted.
Selecon of the operang mode.
-2 MS: Velocity mode Vendor specic velocity mode
-1 MS: Torque mode (from version 03.00) Vendor specic torque mode
Only possible in motor control type 0x2C00 (P300.00) = "Sensorless
vector control (SLVC) [4]" or "Servo control (SC ASM) [2]".
4Torque control w/ freq. limit ^ 206
0 No mode change/no mode assigned No operang mode (standsll)
2 CiA: Velocity mode CiA 402 velocity mode
Addional funcons
Holding brake control
"Automac" brake mode (automac operaon)