EasyManua.ls Logo

Lenze i55AE155F - Page 691

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Designaon Default seng Category Data type Factor A M
0x2D4B:002
(P308.02)
Motor overload monitoring (i²*t): Speed compensa-
on
On [0] general U8 1 P -
0x2D4B:003
(P308.03)
Motor overload monitoring (i²*t): Response Fault [3] general U8 1 P -
0x2D4B:005 Motor overload monitoring (i²*t): Thermal load - (Read only) general U16 1 - -
0x2D4F
(P123.00)
Motor ulisaon (i²*t) x % (Read only) general U16 1 O t
0x2D66:001
(P721.01)
Mains failure control: Enable funcon Disabled [0] general U8 1 P -
0x2D66:002
(P721.02)
Mains failure control: DC-bus acvaon level 0 % * general U8 1 P -
0x2D66:003
(P721.03)
Mains failure control: Gain V-controller 0.01000 Hz/V general U16 100000 P -
0x2D66:004
(P721.04)
Mains failure control: Reset me V-controller 20 ms general U16 1 P -
0x2D66:005
(P721.05)
Mains failure control: DC voltage setpoint 100 % general U8 1 P -
0x2D66:006
(P721.06)
Mains failure control: Setpoint ramp 20 ms general U16 1 P -
0x2D66:007
(P721.07)
Mains failure control: Clear me 20 ms general U16 1 P -
0x2D66:008
(P721.08)
Mains failure control: Restart threshold 0.0 Hz general U16 10 P -
0x2D66:009
(P721.09)
Mains failure control: Status mains failure control - (Read only) general U8 1 O t
0x2D67:001
(P329.01)
Maximum torque monitoring: Response No response [0] MCTRL U8 1 P -
0x2D67:002
(P329.02)
Maximum torque monitoring: Triggering delay 0.000 s MCTRL U16 1000 P -
0x2D81:001
(P151.01)
Life-diagnosis: Operang me x s (Read only) general U32 1 T -
0x2D81:002
(P151.02)
Life-diagnosis: Power-on me x s (Read only) general U32 1 T -
0x2D81:003
(P151.03)
Life-diagnosis: Control unit operang me x ns (Read only) general U64 1 T -
0x2D81:004
(P151.04)
Life-diagnosis: Main switching cycles - (Read only) general U32 1 - -
0x2D81:005
(P151.05)
Life-diagnosis: Relay switching cycles - (Read only) general U32 1 - -
0x2D81:006
(P151.06)
Life-diagnosis: Short-circuit counter - (Read only) general U16 1 - -
0x2D81:007
(P151.07)
Life-diagnosis: Earth fault counter - (Read only) general U16 1 - -
0x2D81:008
(P151.08)
Life-diagnosis: Clamp acve - (Read only) general U16 1 - -
0x2D81:009
(P151.09)
Life-diagnosis: Fan operang me x s (Read only) general U32 1 T -
0x2D84:001
(P117.01)
Heatsink temperature x.x °C (Read only) general I16 10 O -
0x2D84:002 Heatsink temperature: Warning threshold 80.0 °C * general I16 10 P -
0x2D87
(P105.00)
DC-bus voltage x V (Read only) general U16 1 O t
0x2D88
(P104.00)
Motor current x.x A (Read only) general I16 10 O t
0x2D89
(P106.00)
Motor voltage x VAC (Read only) general U16 1 O t
0x2DA2:001
(P108.01)
Output power: Eecve power x.xxx kW (Read only) general I32 1000 O t
* Default seng depending on the size. Firmware version 05.00.00.00
Appendix
Parameter aribute list
691