98
9 FIRMWARE UPDATE FUNCTION
9.1 Update Using an SD Memory Card
Precautions
Back up the various data such as the programs and parameters before executing the firmware update.
Check the target model, and download the correct firmware update file from the Mitsubishi Electric FA website. The
firmware will not be updated if the target model does not match.
Do not change the data (folder and file name) downloaded from the Mitsubishi Electric FA website.
Do not turn the power OFF or reset the CPU module while the firmware update is in progress. Doing so may cause
programs to be deleted.
Do not remove the SD memory card while the firmware update is in progress. If the SD memory card is removed before the
firmware update finishes, the process may end with an error.
When the firmware version of the CPU module is updated by the firmware update function, some functions have restrictions
depending on the serial No. For details on operation, refer to Page 942 Added and Enhanced Functions.
To update the firmware of the CPU module to version "1.100" or later, use the CPU module with serial No. as follows.
- FX5UC-32MT/DS-TS and FX5UC-32MT/DSS-TS: Serial No.178****
- FX5U/FX5UC CPU module other than the above: Serial No.17X****
For the FX5U/FX5UC CPU module with the serial No. 2114001 or later, downgrading to previous firmware version "1.220"
or earlier cannot be performed. Update error (3040H) will occur and the firmware will not be updated.
For the FX5UJ CPU module with the serial No. 2154001 or later, downgrading to previous firmware version "1.010" or
earlier cannot be performed. Update error (3040H) will occur and the firmware will not be updated.
For the FX5UJ-MT/D and the FX5UJ-MR/D, downgrading to previous firmware version "1.050" or earlier cannot be
performed. Update error (3040H) will occur and the firmware will not be updated.
Troubleshooting
If an error occurs, take corrective action according to the error code. (Page 782 List of error codes)
If the error cannot be judged by the error code, check the following items and troubleshoot the situation.
Procedure Error details Action
1 The LED turns off and does not blink. Check that the SD memory card is inserted.
If the FX5S CPU module is used, check that the SD memory card module is mounted.
Check whether the folder name and file name to be stored in the SD memory card are
correct.
Check whether the same firmware version has already been written in.
Obtain the firmware update file from the Mitsubishi Electric FA website, and update the file in
the SD memory card.
2 The RUN LED turns off and the ERR LED is
blinking.
Reset the CPU module. If the same situation occurs again, the hardware of the CPU module
may be malfunctioning. Consult your local Mitsubishi Electric representative.