25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
High-speed counter (pulse density measurement mode)
The pulse density measurement mode for high-speed counters is explained below. The pulse density measurement mode is
not supported in high-speed pulse input/output modules.
When in pulse density measurement mode, pulse is counted from count input of the high-speed counter, and the number of
pulses for a specified amount of time is automatically counted.
Parameter setting
Set operation mode to pulse density measurement mode by high-speed counter parameter setting.
Sets detailed settings for channel used.
Navigation window [Parameter] [Module model name] [Module Parameter] [High Speed I/O] "Input
Function" "High Speed Counter" "Detailed Setting" "Basic Settings"
Window
Displayed items
Item Description Setting range Default
Use/Not Use Set whether use counter or not. Disable
Enable
Disable
Operation Mode Set operation mode. Normal Mode
Pulse Density Assumption Mode
Rotation Speed Measurement Mode
Pulse Input Mode Set pulse input mode. 1-Phase 1 Input (S/W Up/Down Switch)
1-Phase 1 Input (H/W Up/Down Switch)
1 Phase 2 Input
2 Phase 1 Multiple
2 Phase 2 Multiple
2 Phase 4 Multiple
Internal Clock (1MHz)
Preset Input Enable/
Disable
Not available for high-speed counters (pulse density measurement
mode).

Input logic
Input Comparison Enable/
Disable
Control Switch
Preset Value