154
19 DATA LOGGING FUNCTION
19.3 Procedure for Using
Setting example
The procedures for using continuous logging and trigger logging are described with Setting example 1 and Setting example 2.
Setting example 1: Continuous logging
The following shows a setting example of collecting device values of D0, D1, and M0 for 10 seconds at 10ms intervals after
data logging execution is started by operating the tool.
Checking the data logging file
Check the saved data logging file (CSV file) by opening it on your personal computer.
Setting item Description
Logging type Continuous logging
File storage format CSV file
Number of records 1000 records
Collection interval Time specification: 10 milliseconds
Logging target data D0, D1, M0
M0
D0
D1
0
0
OFF
ON
10ms 10ms10ms10ms10ms10ms
CSV
GX Works3
CPU module SD memory card
Ethernet cable
Logging Logging Logging Logging Logging Logging Logging
CPU Module Logging Configuration Tool
Personal computer
[LOGGING]
DATETIME[YYYY/MM/DD hh:mm:ss.sss]
TIME
FX5CPU_2
INTERVAL
INTERVAL[us]
3
INDEX
INDEX
4
SHORT[DEC.0]
D0
5
SHORT[DEC.0]
D1
2
BIT[1;0]
M0
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
2022/4/1 0:31
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
4001
4002
4003
4004
4005
4006
4007
4008
4009
4010
16111
16158
16204
16250
16296
16343
16389
16435
16481
16528
32222
32316
32408
32500
32592
32686
-32758
-32666
-32574
-32480
1
1
1
1
1
1
0
0
0
0
Logging test