31 POSITIONING INSTRUCTION
31.8 Single-table Operation
483
31
Outline of operation
Operand specification
When FX5 operand is specified
1. For (d), specify an axis number for which pulses are output.
Specify an axis number whose positioning parameters are set in the high speed I/O parameters. Operation cannot be
performed if any other axis number is specified.
FX5S/FX5U/FX5UC CPU module: K1 to K4 (Axis 1 to Axis 4)
FX5UJ CPU module: K1 to K3 (Axis 1 to Axis 3)
2. For (n), specify the table number (1 to 100
*1
) that is executed in the axis specified in (d).
*1 1 to 32 when the positioning table data is not set to use device
When the FX3 compatible operand is specified
1. For (d), specify the pulse output number.
Specify an output device (Y) number set in the high speed I/O parameters. (Page 382 Pulse Output Mode) Operation
cannot be performed if any other axis number is specified.
FX5S/FX5U/FX5UC CPU module: Y0 to Y3 (equivalent to axes 1 to 4)
FX5UJ CPU module: Y0 to Y2 (equivalent to axes 1 to 3)
2. For (n), specify the table number (1 to 100
*1
) that is executed in the axis specified in (d).
*1 1 to 32 when the positioning table data is not set to use device
Relation with the DRVTBL and DRVMUL instructions
With the TBL instruction, only the specified table can be activated. Only the complete flag common with other instructions
operates.
With one DRVTBL instruction, multiple tables can be activated. In addition, the table execution method can be selected
from the stepping operation and continuous operation. (Page 490 Multiple-table Operation)
With the DRVMUL instruction, tables for up to four axes can be activated at the same time. (Page 499 Multiple-axis
Table Operation) In addition, by indirectly specifying table numbers, continuous operation can be performed.
For the DRVTBL and DRVMUL instructions, user-specified complete flags can be specified.
Operation of the complete flags
The operation timing of the complete flags depends on the table control method. (Page 417 Complete flag)
TBL (d) (n)
Drive
contact